Eaton 9315 Series UPS Brochure
The Eaton 9315 is a three-phase UPS system available in 225-750 kVA modules. It offers high reliability and flexibility with features like Powerware Hot Sync technology for paralleling systems up to 3324 MW. The 9315 provides double-conversion online protection, advanced battery management with DC Expert, and network connectivity options for critical applications.
Eaton 9315 UPS
The Eaton 9315 is a highly reliable and flexible three-phase UPS system. It is available in single modules ranging from 225 kVA to 750 kVA. The 9315 can be configured in parallel for both redundancy and increased capacity, utilizing the patented Powerware Hot Sync technology, supporting systems up to 3324 MW.
The pursuit of 100 percent availability
In today’s business environment, where technology is critical for survival, IT and facility managers face increasing pressure to achieve zero downtime. As availability requirements grow, so does the demand for the most dependable power protection systems with advanced technology. Eaton has over 40 years of experience addressing the need for maximum uptime in critical systems.
The Eaton 9315 UPS
The 9315 UPS series offers maximum flexibility, reliability, and system availability for enterprises of all sizes. It combines robust hardware, sophisticated power management software, a wide array of accessories and options, and world-class service to deliver a power solution that ensures system availability, allowing businesses to focus on their core operations.
The 9315 is available in these system configurations:
- Single module – reverse transfer
- Multi-module – Powerware Hot Sync – redundant
- Multi-module – Powerware Hot Sync-capacity
Applications
- Data centers
- Server farms
- Telecommunication installations
- Internet service providers
- Transportation systems
- Security operations
- Broadcasting and entertainment
- Process control equipment
- Financial systems
- Credit card operations
- Medical / healthcare
- Industrial systems
Features and benefits
Double-conversion technology
This online double-conversion technology shields the critical load from all input power fluctuations.
DC Expert
Monitors and maintains battery health, providing state-of-charge and dynamically updating battery time remaining information.
Network access
Optional adapters offer LAN connectivity and SNMP compatibility.
Remote notify
The UPS can initiate an outcall for user-selected events.
Intelligent input
Provides superior generator interface and enhanced isolation between input and output.
Intelligent design
A reduced component count significantly minimizes single points of failure.
Monitor panel
Features single-button controls for easy access to UPS status data.
Intelligent controls with DSP
Digital signal processing ensures a more pristine output signal.
True PWM technology
High-speed DSP allows IGBTs to operate at peak capacity, increasing system reliability and guaranteeing perfect power output.
Powerware Hot Sync
This patented paralleling technology eliminates the need for communication between modules, removing a system-level single point of failure. It is available for both redundant and capacity systems.
FORESEER
The FORESEER Enterprise Management System is designed for proactive monitoring and management of critical facility infrastructure. It supports various equipment from different manufacturers, including UPS systems, air handlers, battery monitoring, and environmental sensors. Its advanced graphical user interface and performance analysis tools provide insights to identify trends, implement corrective actions, and prevent failures.
Intelligent Input Filter
The 9315’s Intelligent Input Filter mitigates harmonic distortion and automatically deactivates when necessary, such as during a switch from utility to generator power. Its self-configuring and self-activating nature ensures continuous protection for critical systems against power anomalies.
Eaton 9315 (225-300 kVA)
The 225-300 kVA models feature:
- Monitor panel: A full-size liquid crystal display offering graphical performance data, statistics, alarm history, and metering.
- Control panel: An intuitive control panel for one-button start-up (with optional battery breaker), bypass transfer control, and input circuit breaker operation.
- Communication panel: An external interface supporting remote monitoring and configuration via network or direct connection, including internal modem option, RRS-232 and accessory ports, remote terminal capabilities, X-slot cards, and programmable building alarms for UPS remote control.
Additional features include:
- A large, easy-to-read 7.5″ x 6″ (191mm x 152mm) LCD with push-button controls and a user-friendly Windows interface.
- DC Expert for state-of-charge and battery time remaining updates.
- Operational metering with True RMS sensing for voltage and current, real-time display, and access to up to 400 recent events via modem.
- System performance statistics covering UPS and bypass availability, on-battery conditions, building alarms, and time on bypass.
Eaton 9315 (225-300 kVA) – Internal View
With safety shields removed, the internal components include:
- Redundant power supplies for control logic, ensuring reliable online operation and providing local/remote failure notifications.
- Intelligent controls with digital signal processing, delivering 5% output THD, ±1% output voltage regulation, programmable operating limits, and fail-safe make-before-break bypass transfers.
- A static switch assembly removable for servicing without interrupting the critical load, featuring quick disconnects for safe access.
- Standard dual feed inputs for 480V and 400V (optional for other voltages) enhance availability.
- A 2x-rated neutral supports higher currents from non-linear loads.
- An Intelligent Input Filter that disconnects from the rectifier input during utility loss and low load conditions, improving generator compatibility.
- Mechanical connectors on all input and output terminals reduce installation time.
- Redundant fans provide consistent cooling, quiet operation, and local/remote failure notification, supporting full operational rating up to 5000 without derating.
- A modular design with serviceable components within a 12″ (305mm) depth, requiring only front access for maintenance and achieving low mean time-to-repair.
- Nine-inch removable wireway sections facilitate installation.
Further features include:
- Intelligent alarm management with an event record distinguishing informational notices from operator-required interventions.
- LEDs for at-a-glance UPS operating status, in addition to the LCD panel.
- A hinged access cover protecting an emergency power-off (EPO) button that quickly de-energizes the UPS and critical load.
- Maintenance-free, cold-welded connections securing all power wiring to magnetics, eliminating the need for periodic fastener retorquing and rear access.
- Standard top or bottom entry for installation flexibility.
- Reduced height for 9315 (200-300 kVA) from 65″ (1654mm) to 56″ (1422mm).
- Reduced height for 9315 (300-500 kVA) from 74″ (1880mm) to 65″ (1654mm).
Eaton 9315 (625-750 kVA)
Internal view of the 625-750 kVA models, including a module bypass cabinet for reverse transfer systems, a mimic screen, and an event history log.
Eaton 9315-750
The 9315-750 expands the 9315 family with a single module 750 kVA UPS, featuring a 12-pulse rectifier, high efficiency, a high-speed PWM IGBT inverter, an input isolation transformer, and multi-module system capabilities.
Input/Rectifier Section
- Top cable entry and a dedicated wireway area (cover panel removed in illustration).
- A motor-operated input circuit breaker automatically manages transfers between operational modes.
- An optional inrush current limiter restricts inrush current to 100% of the UPS module rated current.
- The communication panel offers a user-friendly interface for one-button start-up (with optional battery breaker), bypass transfer control, and input circuit breaker operation.
- An optional Intelligent Input Filter disconnects from the rectifier input during utility loss and low load conditions, enhancing generator compatibility.
Output/Inverter Section
- High-speed IGBT, PWM inverter section.
- Redundant fans ensure consistent cooling, quiet operation, and provide local/remote failure notification.
- A motor-operated output circuit breaker automatically manages transfers.
DC Expert battery management (200-500 kVA)
DC Expert provides real-time insights into battery string health and remaining runtime. This feature allows for proactive battery maintenance planning, preventing unexpected load losses due to battery degradation. DC Expert’s battery testing methodology is designed for superior accuracy and assurance compared to other manufacturers.
During a battery test, the rectifier maintains DC link voltage, ensuring consistent battery discharge power month over month.
DC Expert battery test method
- Consistent testing provides battery runtime information accurate to within +/-3%.
- Battery time remaining automatically updates with load shedding during utility outages.
- Battery string health is assessed through periodic testing.
- Programmable, automatic monthly testing can be scheduled for any day and time.
- Monthly tests involve very light battery discharges, consuming less than 10% of available battery runtime, ensuring readiness for utility outages.
- Light load testing does not negatively impact battery life.
- The rectifier remains active during battery testing, sharing the load with the battery for consistent testing regardless of inverter load.
- The critical load remains protected during battery testing as the rectifier does not shut off. If a battery fails during a test, the system will recover 100%.
- DC Expert logs the results of the last 30 tests for trend analysis.
- Supports both valve-regulated (maintenance-free) and wet cell batteries.
Other UPS manufacturers’ battery test methods
- Other UPS manufacturers typically turn off the rectifier to initiate battery testing.
- The battery is solely responsible for supporting the inverter load.
- Battery load varies with changes in the critical load between tests.
- Inconsistent battery test loads lead to inaccurate battery runtime estimates.
- If a battery fails during testing, the inverter must perform an emergency transfer to bypass to avoid dropping the critical load.
With technology essential for 24/7 operations, power protection has evolved from a secondary concern to a critical component of an organization’s technology infrastructure. The 9315 offers various power systems designed to integrate with your technology and meet your availability needs.
Powerware Hot Sync technology
Critical loads require enhanced protection. Eaton developed a unique paralleling system that provides redundancy and capacity with high system availability. Powerware Hot Sync technology minimizes system risks. Unlike traditional paralleling systems that rely on communication between modules for synchronization, load sharing, and selective tripping, which can introduce a system-level single point of failure, Powerware Hot Sync eliminates this need. Each UPS module can independently synchronize and support the critical load, removing the traditional single point of failure.
Powerware Hot Sync-redundant (225-500 kVA modules)
Powerware Hot Sync-redundant
This two-module system delivers exceptional system reliability and availability. It allows for full maintenance on both modules and the parallel cabinet without requiring an external maintenance bypass or interrupting the critical load’s conditioned power. This capability is unique among UPS manufacturers.
Powerware Hot Sync-capacity
This system topology supports up to eight modules in parallel, catering to larger and more critical applications. Advanced monitoring and automated controls ensure ease of operation, comparable to a single-module system.
Powerware Hot Sync-capacity (225-750 kVA modules)
The 9315 offers scalability, allowing effortless expansion from a single module system to a two-module Powerware Hot Sync redundant system, and further to an eight-module Powerware Hot Sync capacity system, providing flexibility for future needs.
Powerware Sync Control Technology
This optional feature enables the seamless transfer of critical loads between two separate UPS system outputs (single module or Powerware Hot Sync capacity systems). Through downstream solid-state transfer switches, Powerware Sync Control Technology synchronizes the outputs, allowing automatic transfer between UPS systems. This ensures that critical loads remain supported by UPS-grade power 24/7, even during scheduled or unscheduled maintenance. The technology also provides remote monitoring of control operations and alarms.
Powerware Hot Tie Technology
Powerware Hot Tie Technology is ideal for scenarios with two UPS systems powering separate loads, enabling load transfer between units for continuous protection. It is particularly beneficial when combined with Powerware Hot Sync Technology, offering an even greater level of redundancy and protection for paralleled systems.
Powerware Hot Tie operates in five modes:
- Normal mode: The tie is open, and the output is synced to bypass.
- Parallel mode: The tie is closed, and the output is synced to one of the UPS bypasses.
- Combined load mode: The tie is closed, and one UPS is operating in service mode.
- System isolation mode: The tie is open, and loads and UPS are removed from the isolated load bus.
- Automatic mode: The tie is continuously available, providing dual power path redundancy without limitations for scheduled maintenance.
Powerware Sync Control (225-750 kVA modules)
Accessories
Maintenance bypass module (MBM)
This floor-mounted, enclosed cabinet provides continuous support for critical loads during UPS module servicing or testing. It includes the maintenance isolation breaker (MIS) and maintenance bypass breaker (MBP).
Power distribution module (PDM)
The PDM distributes output power from the UPS to critical applications. Each PDM consists of two panels, each with 42 poles that can be configured as needed. Additional distribution capacity can be achieved by daisy-chaining these cabinets.
Remote monitor panel (RMP)
The RMP allows customers to monitor the UPS system’s operational status from virtually any location within a facility. It uses simple backlit status indicators and an alarm horn to alert users to changes in the UPS system’s operational status. Multiple RMPs can be installed throughout a facility.
Relay interface module (RIM)
The RIM provides a critical communication link for enhanced reliability, utilizing serial interface and relay contact closures to support up to eight critical loads. It notifies users of operational status changes, enabling timely responses.
Service Plans
The 9315 is backed by Eaton’s comprehensive service plans, ensuring system uptime, convenience, and value. Services cover the UPS, batteries, and related equipment, including remote monitoring and onsite support tailored to specific site or application requirements. The Customer Reliability Center operates 24/7 to monitor systems and respond to needs, with factory-trained service technicians available globally for prompt and reliable service.
Additional service offerings
- Installation and project management.
- A full range of power system maintenance plans (including parts and labor) to suit various needs, from basic UPS and/or battery support to all-inclusive packages for complete peace of mind.
- Remote monitoring services to maximize uptime.
- First responder training for customer employees.
- kVA upgrades and power system enhancements for existing equipment.
- Spare parts kits.
Custom solutions
Eaton offers customized solutions to meet specific customer requirements, identifying the most effective approaches among feasible alternatives to achieve significant cost savings and performance enhancements. Eaton collaborates with engineering firms to design, source, integrate, test, and project manage large systems that may include generators, switchgear, and other electrical products from Eaton or other manufacturers. Dedicated application engineers translate specifications into proposals, project engineers ensure manufacturing, sourcing, integration, and testing, and sales engineers serve as dedicated points of contact. Eaton delivers customized solutions precisely matched to customer needs.
| PRODUCT (kVA MODELS) | 9315-200 (200 kVA) | 9315-225 (225 kVA) | 9315-250 (200-250 kVA) | 9315-300 (225-300 kVA) | 9315-400 (400-500 kVA) | 9315-500 (400-500 kVA) | 9315-625 (500 -625 kVA) | 9315-750 (625-750 kVA) |
| Standard features | ||||||||
| Casters and leveling feet | – | – | – | – | – | – | – | – |
| DC Expert system | ● | ● | ● | ● | ● | ● | – | – |
| Ethernet compatibility | ● | ● | ● | ● | ● | ● | ● | ● |
| Field kVA upgrade capability | – | – | ● | ● | ● | ● | ● | ● |
| Input filter (THD 7%) in U.S. | – | – | – | – | – | – | – | – |
| LCD monitor panel | ● | ● | ● | ● | ● | ● | ● | ● |
| Output isolation | ● | ● | ● | ● | ● | ● | ● | ● |
| Bypass isolation | – | – | – | – | – | – | – | – |
| SNMP capability | ● | ● | ● | ● | ● | ● | ● | ● |
| Token ring compatibility | ● | ● | ● | ● | ● | ● | ● | ● |
| Top and bottom wire entry | ● | ● | ● | ● | ● | ● | – | – |
| ProActive service plan | ● | ● | ● | ● | ● | ● | ● | ● |
| Optional features | ||||||||
| ConnectUPS adapters | ● | ● | ● | ● | ● | ● | ● | ● |
| Hot Sync redundant | ● | ● | ● | ● | ● | ● | – | – |
| Hot Sync capacity | ● | ● | ● | ● | ● | ● | ● | ● |
| Input filter (THD 7%) U.S. | ● | ● | ● | ● | ● | ● | ● | ● |
| Input filter (THD 7%) non U.S. | ● | ● | ● | ● | ● | ● | ● | ● |
| Input isolation transformer | ● | ● | ● | ● | ● | ● | 2 | 2 |
| Internal modem | ● | ● | ● | ● | ● | ● | ● | ● |
| Maintenance bypass panels | ● | ● | ● | ● | ● | ● | ● | ● |
| Output power distribution panels | ● | ● | ● | ● | ● | ● | ● | ● |
| Power management software | ● | ● | ● | ● | ● | ● | ● | ● |
| Relay interface module | ● | ● | ● | ● | ● | ● | ● | ● |
| Remote monitor panel | ● | ● | ● | ● | ● | ● | ● | ● |
| Remote notify | ● | ● | ● | ● | ● | ● | ● | ● |
| Server shutdown via OnliNet/LanSafe | ● | ● | ● | ● | ● | ● | ● | ● |
| SNMP adapters | ● | ● | ● | ● | ● | ● | ● | ● |
Environmental specifications
| Ambient temperature: | 0°C to +40°C |
| Storage: | -20°C to +70°C |
| Relative humidity: | 0-95% non-condensing |
| Altitude: | 1500 meters (5000ft.) at 40°C ambient temperature without load derating |
| Audible noise: | At 1 meter, in accordance with ISO 7778 9315 (225-300 kVA): less than 69dBA 9315 (300-500 kVA): less than 72dBA 9315 (500-750 kVA): less than 75dBA |
| Electrostatic discharge: | Withstands 6 kV (up to 500 kVA withstands 8 kV) without damage or disturbance to the load; exceeds requirements of IEC 801-2 EMC: Meets FCC Class A 5 and EN 50091-2 (CISPR 22, Class A) |
Input specifications
| Voltage range: | (refer to product data sheets) |
| Frequency range: | (60 Hz) 57-63 Hz; (50 Hz) 47-53 Hz |
| Surge protection: | Meets IEEE 587, Category A & B, EN 50091-2 and EN 50082-2 |
| Power factor: | 0.95 typical at full load with optional input filter Input current distortion less than 7% typical with optional input filter |
Output specifications
| Output voltage THD: | (linear load): less than 3% for a 100%; (linear load); 2% for a single harmonic; Output voltage THD (non-linear): less than 5% when tested in accordance with EN50091-3. |
| Voltage regulation: | Better than +1% |
| Transient response: | Less than 5% for 100% load step; full recovery within 1 cycle |
| Frequency: | (Free run) ±0.005 Hz |
| Frequency sync range: | ±0.5 Hz |
| Frequency slew rate: | 1 Hz/second maximum |
| Voltage adjustment range (Operator): | ±5% |
Battery Specifications
| Matching battery type: | Sealed, valve regulated lead acid |
| Recharge time: | 10–12 times the discharge time to 95% |
| Other battery options: | Wet cell and nickel-cadmium batteries; open racks available |
Safety
UL1778 Listed
UL CAN/CSA C22.2 NO.107.1 Listed, EN 50091-1
All cabinets provide seismic mounting features
Selectable DC ground fault detection capability
To learn more about the 9315, please visit: Eaton.com/powerquality.